Mitsubishi PLC รุ่น FX2N-4AD
Description
Analog output :
Analog output range
Voltage output : DC-10V to + 10V (External load resistance 2kΩ to 1MΩ)
Current output : DC 0mA to + 20mA (External load resistance 500Ω or less)
Number of output channels : 4 channels
Output characteristics : The output mode (voltage / current output) can be set for each channel.
Digital input
Voltage output : 11bit binary + sign 1bit
Current output : 10bit binary (unsigned)
Resolution
Voltage output : 5mV (10V x 1/2000)
Current output : 20μA (20mA × 1/1000)
Overall accuracy
Voltage output : ± 1% (± 0.2V) for full scale 20V (Excludingload fluctuation)
Current output : ± 1% (± 0.2 mA) for full scale 20 mA
D / A conversion time : 2.1ms / 4 channels (regardless of the number of channels used)
Insulation method : The analog output section and sequencer are isolated by a photocoupler The analog output section and power supply are isolated by a DC / DC converter Each channel is not isolated
Number of occupied I/O points : 8 points (can be counted by either input or output)
Applicable sequencer : FX2N, FX3U, FX2NC, FX3UC
Mass : 0.3kg
Power supply : 5V 30mA (Internal power supply from PLC) DC24V ± 10% 200mA (External power supply)