Ambient temperature : 0 ~ 55 ℃ ・ ・ ・ Operating -25 ~ 75 ℃ ・ ・ ・ Storage
Relative humidity : 5 to 95% RH (no condensation) ······· Operating
Vibration resistance
When mounting DIN rail
Frequency: 10-57Hz /Single amplitude: 0.035mm 10 times in each of X, Y, Z directions (total 80 minutes each)
Frequency: 57-150Hz /Acceleration: 4.9m / s 2 10 times in each of X, Y, Z directions (total 80 minutes each)
Direct mounting
Frequency: 10-57Hz /Single amplitude: 0.075mm 10 times in each of X, Y, Z directions (total 80 minutes each)
Frequency: 57-150Hz /Acceleration: 9.8m / s 2 10 times in each of X, Y, Z directions (total 80 minutes each)
Shock resistance : 147m / s 2 , working time 11ms, sine half-wave pulse 3 times each in X, Y, Z directions
Noise resistance : Using a noise simulator with a noise voltage of 1,000 Vp-p, a noise width of 1 μs, a rise of 1 ns, and a period of 30 to 100 Hz
Withstand voltage : Between all external terminals and ground terminal: 500 VAC for 1 minute
Insulation resistance : Between external terminals and ground terminal: 5MΩ or more with DC500V insulation resistance meter
Ground : Class D grounding (Grounding resistance: 100Ω or less)
Usage atmosphere : There is no corrosive or flammable gas, and the conductive dust (dust) is not severe.
Usage altitude : Cannot be used in an environment pressurized to 2000m or less and atmospheric pressure. There is a possibility of failure.