Ambient temperature : 0 ~ 55 ℃ ・ ・ ・ Operating, -20 ~ 70 ℃ ・ ・ ・ Storage
Relative humidity : 35% to 85% (with no condensation): Operating
Vibration resistance
When mounting DIN rail
Frequency: 10-57Hz
Half amplitude: 0.035 mm X, Y, Z each direction 10 times (total each 80 minutes) criteria, according to IEC61131-2
Frequency: 57-150Hz
Acceleration: 4.9 m / s 2 X, Y, Z each direction 10 times (total each 80 minutes) criteria, according to IEC61131-2
Direct mounting
Frequency: 10-57Hz
Half amplitude: 0.075 mm X, Y, Z each direction 10 times (total each 80 minutes) criteria, according to IEC61131-2
Frequency: 57-150Hz
Acceleration: 9.8m / s 2 10 times in each of the X, Y, and Z directions (total of 80 minutes each) Judgment criteria are based on IEC61131-2
Noise resistance : Using a noise simulator with a noise voltage of 1,000 Vp-p, a noise width of 1 μs, a rise of 1 ns, and a period of 30 to 100 Hz
Withstand voltage : When performing a withstand voltage test, perform the following voltage between each terminal and the ground terminal of the basic unit. Between power supply terminal (AC power supply) and ground terminal: AC1.5kV for 1 minute Between input terminal (AC100V) and ground terminal: AC1.5kV for 1 minute Between output terminal (relay) and ground terminal: AC1.5kV for 1 minute
Insulation resistance : When performing an insulation resistance test, perform the following voltage between each terminal and the ground terminal of the basic unit. Between power supply terminal (AC power supply) and ground terminal: 5 MΩ or more with DC500V insulation resistance meter Between input terminal (AC100V) and ground terminal: 5MΩ or more with DC500V insulation resistance meter Between output terminal (relay) and ground terminal: DC500V insulation resistance 5MΩ or more in total
Ground : Class D grounding (Grounding resistance: 100Ω or less)
Usage atmosphere : There is no corrosive or flammable gas, and the conductive dust (dust) is not severe.
Usage altitude : Cannot be used in an environment pressurized to 2000m or less and atmospheric pressure. There is a possibility of failure.